The Bar IVF Unit
B The BarIVF unit · Plan C

Third-floor IVF unit · Saudi MOH Level III-IVF

The Bar · Plan C

The agreed design for a two-theatre IVF unit sized for 2,000–3,000 cycles a year. It meets the Saudi MOH Level III-IVF requirements first, then the iHFG Part B IVF Unit and the Saudi Building Code for fire, with a true L-shaped embryology lab beside a 22.8 m² cryo room.

2,000–3,000cycles a year (2,050 busy-day ceiling at standard hours)
2 ORs40.7 and 40.3 m², hatches to the lab
4 + 8Stage I bays and VIP rooms with en-suite WC
≈91 m²true L embryology lab + 18 m² ICSI & biopsy
≈22.8 m²cryo room, 3.5 m LN₂ auto-fill line
4 + 6ultrasound rooms and consult rooms in the OPD

Why Plan C works

  • One secured lab zone with a single gowned entry; eggs pass from both ORs by hatch.
  • Every egg and embryo carry in the lab is under 4 m.
  • Cryo sits across the corridor from the gas room: a 3.5 m LN₂ line, nothing over cryo.
  • Every room and corridor meets its MOH or iHFG minimum; bed routes are at least 2.44 m clear.
  • Clean supplies and waste never share a lift or a route.
  • Smaller HEPA area than the initial design, with one andrology lab and the hospital CSSD.

Compliance at a glance

Design, MEP and fit-out items only. Staffing, forms and contracts are for the client.

Open before construction

  • Fire consultant: smoke compartments, door schedule and the 43 m route from VIP 1 against SBC 801.
  • Structural engineer: floor load under the cryo dewars (≈7.5–10 kN/m²).
  • MEP: pressure cascade, gas and LN₂ routes in the ceiling void, backup power.
  • MOH: written acceptance of 2 interview rooms instead of 3.
  • Storage: one large vapour-phase tank or a renewal policy for a 10-year horizon.